4 Control requirements<br>4.1 Unit start-up, shutdown<br>Before the start of the unit, open the trap on the hydrophobic branches. When the load rises to 25%, close the trap. When the load is stopped or reduced, when the load is reduced to 25%, open the trap and display it with light in the control room.<br>4.2 When the turbine accident tripping stops, the trap on each hydrophobic branch should be opened.<br>4.3 When the low-pressure heater is out of service, the corresponding section trap should be opened.